PLP-Series 3/4" Now Available! - 2 inches of height for up to 6 inches WC pressure

HVAC Air-Trap RLC Series - Waterless HVAC Condensate Trap - Des Champs Technologies
HVAC Air-Trap RLC Series Clear - Waterless HVAC Condensate Trap - Des Champs Technologies
HVAC Air-Trap RLC Series White - Waterless HVAC Condensate Trap - Des Champs Technologies
RLC-Series Air-Trap™: Residential/Lite Commercial Negative/Positive Waterless HVAC Condensate Trap allows liquid condensate to drain from the HVAC equipment and simultaneously prevents air from entering or escaping from the equipment. From Des Champs Technologies.
RLC-Series Air-Trap™: Residential/Lite Commercial Negative/Positive Waterless HVAC Condensate Trap allows liquid condensate to drain from the HVAC equipment and simultaneously prevents air from entering or escaping from the equipment. From Des Champs Technologies.
HVAC Air-Trap RLC Series Clear Installation - Waterless HVAC Condensate Trap - Des Champs Technologies
HVAC Air-Trap RLC Series Clear Installation - Waterless HVAC Condensate Trap - Des Champs Technologies
HVAC Air-Trap RLC Series Clear Installation - Waterless HVAC Condensate Trap - Des Champs Technologies
HVAC Air-Trap RLC Series Clear Installation - Waterless HVAC Condensate Trap - Des Champs Technologies

RLC-Series Air-Trap™: Residential/Lite Commercial Negative/Positive Waterless HVAC Condensate Trap

Regular price $36.00 Sale

Volume Pricing is Available - Please email info@waterless-trap.com for a discount code.

Never Freezes - Never “Dries” Out!

The Air-Trap™ allows liquid condensate to drain from the HVAC equipment and simultaneously prevents air from entering or escaping from the equipment.

Patented US10775073B2

Des Champs Technologies, LLC has recently introduced the versatile RLC Series HVAC Air-Trap. The HVAC Air-Trap uses the air pressure generated by the fan, or gravity, to prevent air leakage from or to the air handler. The RLC Series can accommodate PVC drain pipe sizes from ½" to 2" and up to 40 tons of refrigeration.

When oriented in the horizontal position it can accommodate essentially any HVAC unit negative plenum pressure and requires less than half the installation height of a standard P-trap. The lower height allows ease of installation and in many cases, reduces curb height requirements or in some cases eliminates the need for a curb. In addition, the RLC Series eliminates the following issues associated with the P-trap:

  • Never requires priming or filling with water
  • Since it operates dry when there is no condensate being produced, the trap and the drain line leading to the trap will not freeze
  • There will be no geyser effect within the HVAC unit at the beginning of cooling season as is common with a dry P-trap
  • Because the trap operates dry when no condensate is flowing there will be no accumulation of sludge
  • The HVAC Air-Trap is predesigned so errors caused by field designed P-traps are eliminated
HVAC Air-Trap™ Waterless HVAC Condensate Trap by Des Champs Technologies
When the unit fan is blowing through the cooling coil the drain pan is under positive pressure. Under these conditions the RLC Series is oriented in the vertical position. In the positive pressure mode the maximum pressure in the unit plenum is 3 inches WC. All of the benefits listed above are present when operating in the positive pressure mode plus the blow through that occurs on a dry P-trap is eliminated.
    RLC-Series HVAC Air-Trap™ - Negative/Positive Pressure Waterless Trap allows liquid condensate to drain from the HVAC equipment and simultaneously prevents air from entering or escaping from the equipment.
    RLC-Series HVAC Air-Trap™ - Negative/Positive Pressure Waterless Trap allows liquid condensate to drain from the HVAC equipment and simultaneously prevents air from entering or escaping from the equipment.
    Negative Pressure - Orientation is Horizontal
    • Condensate flow up to 2 GPM at any negative pressure
    • Schedule 40 PVC  with clean out port
    • Retains no water after condensing has ceased
    • ¾” slip internal or 1” fitting external connection - with bushings can connect to ½, 1 ¼,  1 ½ and 2” tubes
    • Meets general building codes. For use on HVAC equipment only.
    RLC-Series HVAC Air-Trap™ - Negative/Positive Pressure Waterless Trap allows liquid condensate to drain from the HVAC equipment and simultaneously prevents air from entering or escaping from the equipment.
    Positive Pressure - Orientation is Vertical
    • Up to 3-inches positive pressure
    • Up to 0.5 GPM water flow (≈ 40 tons)

         Not for use as a sanitary trap.

      Note: The attached drawings represent traps that operate under positive pressure. Never connect condensate drain directly to a sanitary drain line.

      Flammability rating is UL94 V-0

       

       

      Videos: 

       

       

       

      RLC-Series Positive/Negative Orientation Animation

      An animation detailing RLC-Series concept for a positive pressure and negative pressure installation.

       

      HVAC Air-Traps have been ICC-ES Evaluated  The Air-Trap™ concept has been incorporated into IAPMO IGC 196-2018 Standard for Condensate Traps and Overflow Switches for Air-Conditioning Systems.
      ICC-ES Evaluated

      Click to view the PMG-1967 full report from ICC Evaluation Service, LLC

      https://www.iapmomembership.org

      The Air-Trap™ concept has been incorporated into IAPMO IGC 196-2018 Standard for Condensate Traps and Overflow Switches for Air-Conditioning Systems.

       

      Customer Reviews

      Based on 9 reviews
      100%
      (9)
      0%
      (0)
      0%
      (0)
      0%
      (0)
      0%
      (0)
      A
      Austin King
      HVAC Air Trap

      A well made, clever product for a very stubborn issue! Having a very restricted HVAC system design, the air pressure would frequently blow out the trap, causing odors to escape from the bathroom sink where the condensate line was run. The valve works exactly as advertised, and the smell has never returned!

      H
      Homer Montgomery
      No more bad smells

      The condensate drain from our air handler in the attic (new heat pump) kept drying out when using the heat. The inadequate p-trap was buried some place in the wall below it and would regularly dry out permitting sewer gas to be sucked into the system. The solution, one that the “professionals” were not aware of, was the Air-Trap. Installation was simple, and the result was excellent.

      D
      David Solares
      Water trap confusion

      Very happy with the results. No more worry about p trap drying out.

      J
      Justin Jimenez
      Works great, but if your HVAC setup is like mine...

      The trap is high quality and was super easy to install exactly as advertised. With that, my HVAC has a positive pressure condensate drain, and the water stopped draining out the line if there was NOT a decent airflow coming out the P-trap vent stack (i.e. - wasting conditioned air). I solved the problem by looping the vented air back to the intake (return) plenum via 3/4" PVC. With that, water only drains out the RLC, and any "wasted" air is saved by recycling through the blower.

      p
      paradis
      quick delivery; concept makes sense

      received shipment within 2 days from placing order. Installation was straight forward. Trap appears to be well made and functions as described.

      Customer Reviews

      Based on 9 reviews
      100%
      (9)
      0%
      (0)
      0%
      (0)
      0%
      (0)
      0%
      (0)
      A
      Austin King
      HVAC Air Trap

      A well made, clever product for a very stubborn issue! Having a very restricted HVAC system design, the air pressure would frequently blow out the trap, causing odors to escape from the bathroom sink where the condensate line was run. The valve works exactly as advertised, and the smell has never returned!

      H
      Homer Montgomery
      No more bad smells

      The condensate drain from our air handler in the attic (new heat pump) kept drying out when using the heat. The inadequate p-trap was buried some place in the wall below it and would regularly dry out permitting sewer gas to be sucked into the system. The solution, one that the “professionals” were not aware of, was the Air-Trap. Installation was simple, and the result was excellent.

      D
      David Solares
      Water trap confusion

      Very happy with the results. No more worry about p trap drying out.

      J
      Justin Jimenez
      Works great, but if your HVAC setup is like mine...

      The trap is high quality and was super easy to install exactly as advertised. With that, my HVAC has a positive pressure condensate drain, and the water stopped draining out the line if there was NOT a decent airflow coming out the P-trap vent stack (i.e. - wasting conditioned air). I solved the problem by looping the vented air back to the intake (return) plenum via 3/4" PVC. With that, water only drains out the RLC, and any "wasted" air is saved by recycling through the blower.

      p
      paradis
      quick delivery; concept makes sense